(3)‘‘best efficiency point’’ (BEP) means the best energy efficiency point for fan operation, determined at inherent speed;’;
(b)the following definition is added as point (32):
(32)‘‘inherent speed’’ means the rotation speed of the fan impeller, when the fan is operated at its nominal voltage and frequency. In case of fans with a variable speed drive or intended to be used with a variable speed drive, the inherent speed is the maximum speed achieved by the fan or the speed at which the efficiency is declared by the manufacturer, and that is in line with the fan safe operation and in line with the intended use of the fan. Where the motor is a multiple speed motor, the highest speed made available to the customer applies.’